The Occupational Safety, Health and Working Conditions (Andhra Pradesh) Rules, 2026
Schedule VII
Official text
Open in the official PDF (pp. 117–119)
Tables and forms lose their layout when extracted; the PDF is the authoritative version.
GENERATION OF GAS FROM DANGEROUS PETROLEUM
1. Flame traps
The plant for generation of gas from dangerous petroleum and associated
piping and fittings shall be fitted with atleast two efficient flame traps so
designed and maintained as to prevent a flash back from any burner to the
plant. One of these traps shall be fitted as close to the plant as possible.
The plant and all pipes and valves shall be installed and maintained free
from leaks.
2. Generating building or room
All plants for generation of gas from dangerous petroleum erected after the
coming into force of the provisions specified in this schedule shall be
erected outside the factory building proper in a separate well-ventilated
building (hereinafter referred to as the "generating building"). In the case
of such plant erected before the coming into force of the provisions
specified in this schedule there shall be no direct communication between
the room where such plants are erected(herein after referred to as the
"generating room"), and the remainder of the factory building. So far as
practicable, all such generating rooms shall be constructed of fire-resisting
materials.
3. Fire Extinguishers
An efficient means of extinguishing petrol fire shall be maintained in an
easily accessible position near the plant for generation of gas from
dangerous petroleum.
4. Plant to be approved by the Chief Inspector-cum-Facilitator
Gas from dangerous petroleum shall not be manufactured except in a plant
for generating gas from dangerous petroleum, the design and construction
of which has been approved by the Chief Inspector-cum-Facilitator.
5. Escape of dangerous petroleum
Effective steps shall be taken to prevent dangerous petroleum from
escaping into any drain or sewer.
6. Prohibition relating to smoking, etc.,
No person shall smoke or carry matches, fire or naked light or other means
of producing a naked light or sparkin the generating room or generating
building or in the vicinity thereof and a warning notice in the language
understood by the majority of the workers shall he pasted in the factory
prohibiting smoking and the carrying of matches, fire or naked light or
other means of producing a naked light or spark into such room or
building.
7. Access to dangerous petroleum or container
No unauthorized person shall have access to any dangerous petroleum or
to vessel containing or having actually contained (dangerous) petroleum.
8. Electric fittings
All electric fittings shall be of flame-proof construction and all electric
conductors shall either be enclosed in metal conduits or be lead sheathed.
9. Construction of doors
All doors in generating room or generating building shall be constructed to
open outwards or to slide and no door shall be locked or obstructed or
fastened in such a manner that it cannot be easily and immediately opened
from the inside while gas is being generated and any person is working in
the generating room or generating building.
10. Repair of containers
No vessel that has contained petroleum shall be repaired in a generating
room or generating building and no repairs to any such vessel shall be
undertaken unless live-steam has been blown into the vessel and until the
interior is thoroughly steamed out or other equally effective steps have
been taken to ensure that it has been rendered free from dangerous
petroleum or inflammable vapour.