The Occupational Safety, Health and Working Conditions (Andhra Pradesh) Rules, 2026
Schedule XXIII
Official text
Open in the official PDF (pp. 207–212)
Tables and forms lose their layout when extracted; the PDF is the authoritative version.
CARBON DISULPHIDE PLANTS
1. Application
This Schedule shall apply to all electric furnaces in which carbon Disulphide
is generated and all other plants where carbon Disulphide, after generation
is condensed, refined and stored.
These rules are in addition to and not in derogation of any of the provisions
of the Act and the rules made thereunder.
2. Construction, installation and operation
(a) The buildings in which electric furnaces are installed and carbon disulphide
after generation is condensed and refined shall be segregated from other
parts of the factory and shall be of open type to ensure optimum
ventilation and the plant layout shall be such that only a minimum number
of workers are exposed to the risk of any fire or explosion at any one time.
(b) Every electric furnace and every plant in which carbon Disulphide is
condensed, refined and stored with all their fittings and attachments shall
he of good construction, sound material and of adequate strength to
sustain the internal pressure to which the furnace or the plant may be
subjected and shall be so designed that carbon Disulphide liquid and gas
are in closed system during their normal working.
(c) The electric furnace supports shall be firmly grouted about 61 centimeters
in concrete or by other effective means.
(d) Every electric furnace shall be instilled and operated according to
manufacturers' instructions and these instructions shall be clearly imparted
to the personnel in charge of construction and operation.
(e) The instructions regarding observance of correct furnace temperature,
Sulphur dose, admissible current/power consumption and periodical
checking of charcoal level shall be strictly complied with.
3. Electrodes
(a) Where upper ring electrodes made of steel or used in the electric furnace,
they shall be of seamless tube construction and shall have arrangement for
being connected to cooling water system through a hip on built in the
electrodes or through a positive pressure water-pump.
(b) The arrangement for cooling referred to in clause (a) shall be connected
with automatic alarm system which will actuate in the event of interruption
of cooling water in the electrodes and give visible and audible alarm signals
in the control room and simultaneously stop power supply for the furnace
operation and to stop the further supply of water. The alarm system and
the actuating device shall be checked every day.
4. Maintenance of charcoal level
When any electric furnace is in operation, it shall be ensured that the
electrodes are kept coveted with charcoal bed.
5. Charcoal separator
(a) Cyclone type of charcoal separator shall be fitted on the off take pipe
between the electric furnace and Sulphur separator to prevent entry of
pieces of char-coal into the condensers and piping.
(b) Any other design for gas off takes pipe which dues tic• allow charcoal
pieces into the condensers and piping may be adopted.
6. Rupture Discs and Safety Seal
(a) At least two rupture discs of adequate size which shall blow off at a
pressure twice the maximum operating pressure shall be provided on
each furnace and shall either be mounted directly on the top of the
furnace or each through an independent pipe as close as possible to the
furnace.
(b) A safety water seal shall be provided at the best possible location to
ensure the maximum and effective operation of the rupture discs
mentioned in (a) above.
7. Pyrometer and Manometers
(a) Each electric furnace shall be fitted with adequate number of
pyrometers Ito give an indication of the temperature as correctly as
reasonably practicable at various points in the furnace. The dials for
reading the temperature shall be located in the control room.
(b) Manometers or any other suitable devices shall be provided for
indicating pressure
i. In the off take pipe before and after the Sulphur separator; and
ii. In Primary and secondary condensers.
8. Check Valves or Water Seals
All piping carrying carbon Disulphide shall be fitted with check valves or
water seals at suitable positions so as to prevent gas from flowing back
into any electric furnace in the event of its shut down.
9. Inspection and maintenance of Electric Furnaces
(a) Every electric furnace shall be inspected internally by a competent
person
(i) before being placed in service after installation:
(ii) before being placed in service after reconstruction or repairs; and
(iii) periodically every time the furnace is opened for cleaning or (or
replaced electrodes.
In respect of item (iii) if it is felt by operators that during dashing it is not
necessary to inspect internally so as to conserve the heat in the furnace,
internal inspection can be done away with.
(b) When an electric furnace is shut down for cleaning,
(i) If removal of any part of the lining is resorted to, the condition of
the shell shall be closely inspected, and
(ii) any plates forming shell found corroded to the extent that safety of
the furnace is endangered shall be replaced:
10. Maintenance of Records
The following hourly records shall be maintained in a logbook
(i) Manometer reading at the points specified in clause (b) of rule7.
(ii) Gas temperature indicated by pyrometers and all other vital points
near the Sulphur separator and primary and secondary condensers.
(iii) Water temperature and flow of water through the siphon in the
electrodes.
(iv) Primary and secondary voltages and current and energy consumed.
11. Electrical apparatus, wiring and fittings
All buildings in which carbon disulphide is refined or stored shall be
provided with electrical apparatus, wiring and fittings which shall afforded
equate protection from fire and explosion.
12. Prohibition relating to smoking
No person shall smoke or carry matches, fire or naked light or other means
of producing a naked light or spark in buildings in which carbon Disulphide
is refined or stored, and a notice in the language under-stood by a majority
of the workers shall be posted in the plant prohibiting smoking and
carrying of matches, fire or naked light of other means of producing naked
light or spark into such rooms.
13. Means of escape
Adequate means of escape shall be provided and maintained to enable
persons to move to a safe place as quickly as possible in case of an
emergency. At least two independent staircases of adequate width shall be
provided in every building housing the furnaces at reasonable intervals at
opposite ends. These shall always be kept clear Mall obstructions and so
designed as to afford easy passage.
14. Warnings Incase of fire
There shall be adequate arrangements for giving warnings in case of fire or
explosion which shall operate on electricity and, in case of failure of
electricity, by some mechanical means.
15. Fire fighting equipment
(a) Adequate number of suitable fire extinguishers or other fire-fighting
equipment shall be kept in constant readiness for dealing with risks
involved and depending on the amount and nature of materials stored:
(b) Clear instructions as to how the extinguishers or other equipment should
be used shall be printed in the language which the majority of the workers
employed understand. The instructions shall be affixed to each
extinguisher or other equipment and the personnel trained in their use
shall be supplied with the instructions.
16. Bulk Sulphur
(a) Open or semi-enclosed space for storage of bulk Sulphur shall be sited
with due regard to the dangers which may arise from sparks given off
by nearby locomotive, etc., and precautions shall be taken to see that
flames, smoke and matches and other sources of ignition do not come
in contact with the clouds of dust arising during handling of bulk
Sulphur.
(b) All enclosures for bulk Sulphur shall be of non-combustible
construction, adequately ventilated and so designed as to provide a
minimum of ledges on which dust may lodge.
(c) The bulk Sulphur in the enclosures shall be handled in such a manner
as to minimize the formation of dust clouds and no flame, smoke and
matches or other sources of ignition shall be employed during handling
and non- sparking tools shall be used when ever Sulphur is shoveled or
otherwise removed by band.
(d) No repairs involving flames, beat or use of hand or power tools shall be
made in the enclosure where bulk Sulphur is stored.
17. Liquid Sulphur
Open flames, electric sparks and other sources of ignition, including smoke
and matches, shall be excluded from the vicinity of molten Sulphur.
18. Training and supervision
(a) All electric furnaces and all plants in which carbon Disulphide is
condensed, refined or stored shall be under adequate supervision at all
times while the furnaces and plant are in operation.
(b) Workers in charge of operation and maintenance of electric furnaces and
the plants shall be properly qualified and adequately trained.
19. Washing facilities
The occupier shall provide and maintain in a clean state and in good repair,
for the use of all persons employed awash-place under cover with atleast
one tap or stand-pipe, having a constant supply of clean water for every
five such persons, the taps or stand-pipes being spaced not less than 120
centimeters apart with a sufficient supply of soap and clean towels,
provided that towels shall be supplied individually to each worker if so
ordered by the Inspector-cum-Facilitator. All the workers employed in
Sulphur storage handling and inching operations shall be provided with a
nail brush.
20. Personal Protective equipment
(a) Suitable goggles and protective clothing consisting of overalls without
pockets, gloves and foot-wear shall be provided for the use of
operatives:
(i) When operating valves or cocks controlling fluids, etc.
(ii) Drawing off of molten Sulphur from Sulphur pots, and
(iii) Handling charcoal or Sulphur.
(b) Suitable respiratory protective equipment shall be provided and stored
in the appropriate place for use during abnormal conditions or in an
emergency.
(c) Arrangements shall be made for the proper and efficient clearing of all
such protective equipment.
21. Cloak-rooms
There shall be provided and maintained for the use of all persons employed
in the processes a suitable cloak-room for clothing put off during work
hours and a suitable place separate from the cloak-room for the storage of
overalls or working clothes The accommodation so provided shall be placed
in the charge of a responsible person and shall be kept clean.
22. Unauthorized persons: Only maintenance and repair personnel, persons
directly connected with the plant operation and those accompanied by
authorized persons shall be admitted into the plant.