The Occupational Safety, Health and Working Conditions (Andhra Pradesh) Rules, 2026
Schedule XXIX
Official text
Open in the official PDF (pp. 247–261)
Tables and forms lose their layout when extracted; the PDF is the authoritative version.
FLAMMABLE LIQUEFIED OR COMPRESSED GASES AND HIGHLY
FLAMMABLE LIQUIDS
1. Application
Provisions of this Schedule shall apply to all factories where flammable
liquefied or compressed gases or highly flammable liquids are
manufactured, stored, handled used (sic.).
2. Definitions
For the purposes of this Schedule
(a) "bulk storage " means bullet or Horton sphere or mounded vessel or
portable cylinders used for storage of flammable liquefied or
compressed gases or highly flammable liquids, which are having
cumulative water storage capacity exceeding one thousand liters;
(b) "bullet" means a horizontal cylindrical pressure vessel with
hemispherical or dished ends used for storage of flammable liquefied or
compressed gas;
(c) “explosive mixture” means a mixture of combustion agent (oxidizing
substance in gaseous, liquid or solid state) and a fuel (oxidisable
substance in gaseous, liquid or solid state) in such proportions that it
could give rise to a very rapid and violent oxidation reaction, liberating
more kinetic energy than is dissipated through conduction and
convection, ultimately causing practical effect of explosion ;
(d) "fire proof " means a passive means of protection of a structure or
equipment or vessel from exposure to direct fire or flame impingement
or prolonged exposure to high intensity radiant thermal flux, by the
application of a coating of certain heat-resistant substance or mixture
of a specified rating ;
(e) "fire safe " means a provision of dual seating to control leakage to
acceptable level, even after damage, due to fire, as applied to valves
(f) "flammable compressed gas " means flammable compressed gas as
defined in rule 2 of the Static and Mobile Pressure Vessels (Unfired)
Rules, 1981 framed under the Explosives Act, 1884 (Central Act IV of
1884) ;
(g) "flammable liquefied gas " means a flammable gas kept in liquefied
state by the application of pressure at normal ambient temperature,
13% (thirteen percentage) or less of which by volume with air forms a
flammable mixture or which has a flammable range with air of atleast
12% (twelve percentage) points regardless of the lower flammable
limits;
(h) "gas free " means a condition when the concentration of a flammable
gas in an equipment or a vessel is well below the threshold limits
(lower explosive limit), so, that it is safe for a man to enter into the
equipment or vessel or to conduct "hot work " there, as the case may
be ;
(i) "highly flammable liquid " means any liquid including its solution,
emulsion or suspension which when tested in a manner specified by
sections 14 and 15 of the Petroleum Act, 1934 (Central Act XXX of
1934) gives off flammable vapors at a temperature less than 32
degrees Centigrade:
(j) "Horton sphere" means a spherical Pressure Vessel, supported
vertically and is used for the storage of flammable liquefied or
compressed gas;
(k) "hot work" means an activity which may produce enough heat or spark
to ignite a flammable or explosive mixture;
(l) "Mounded vessel" means a pressure vessel for the storage of
flammable liquefied or compressed as, which is placed above ground
and is completely covered by a mound of earth or similar inert material
except for nozzles, manhole covers, inspection covers fitted on the top
of the vessel ;
(m) "purging" means an act of replacing the atmosphere inside a vessel
or a container by an inert gas in such a manner as to prevent the
formation of an explosive mixture.
(n) "purging into service" means the replacement of air in a closed system
by an inert gas and then replacement of the inert gas by the flammable
gas, vapour or liquid;
(o) "purging out of service" means the replacement of normal flammable
content of a closed system by an inert gas and then replacement of the
inert gas by air to such an extent that it is gas free and safe for any
person to work ;
(p) "remote operated emergency valve" means a shut-off valve capable of
remote operation which closes automatically on loss of the actuating
power or fire engulfment and which is fire-safe.
3. Storage
Every highly flammable liquid, flammable liquefied or compressed gas used
in every factory shall be stored in bulk in suitable fixed storage tank made
of adequate fire-resistant construction and located in a safe position under
the ground or in the open.
4. Location and spacing
Before selecting the location of any storage vessel, risk analysis study shall
be carried out. Based on the risk analysis study, every storage vessel shall
be located in the manner specified below:
(a) the location shall not interfere with the movement of vehicles. The Risk
Contour shall not intercept the public places such as assembly points,
canteen, rest sheds and similar other locations;
(b) before locating any storage vessel, the soil-condition shall be assessed
for the suitability of the super structure ;
(c) the storage vessel shall be sited above ground in open air and well-
ventilated place ;
(d) mounded vessels shall be so located that the man holes and pressure
relief valves are in a well-ventilated position;
(e) the minimum safety distance between the storage vessels and from
buildings, boundary or fixed ignition source shall be in accordance with
the Static and Mobile Pressure Vessels (Unfired) Rules, 1981, as
amended from time to time ;
(f) the storage vessels shall not be installed one above the other;
(g) the bullets shall be so located that their longitudinal axes do not points
towards other vessels, vital process equipment, control rooms, loading
stations, nearby buildings or storage tanks containing hazardous
materials;
(h) weeds, long grass, deciduous shrubs and trees and any combustible
materials shall be removed from the storage vessel area within the
licensed premises;
(i) the storage vessels shall not be located within the blinded enclosure of
any heat source or other flammable liquids, gases or oxidizers ;
(j) the storage vessels, pumping equipment, loading and unloading
facilities and vaporizers shall be located in an exclusive fenced
compound of atleast 2 meters high along the perimeter of the safety
zone'; such fenced compound shall have atleast two gates for the safe
exit of persons and vehicles in case, of any emergency ;
(k) the number of storage vessels in one group shall not exceed six;
(l) storage vessels within a group shall be so located that their longitudinal
axes are parallel to each other;
(m) spheres and bullets shall not be grouped together and shall be
provided with separate piping manifold, so as to avoid over filling of a
vessel due to gravitation from the other;
(n) the top surface of the storage vessels installed in a group shall be on
the same plane so that the pressure safety valve blow-out from them
do not affect the other;
(o) the flooring of the bullets or spheres shall be sloped in such a way that
the spilled liquid or gas from any vessel shall not pass through any
other vessel;
(p) the storage vessels shall not be located in such a way that the high
tension electrical cables shall not pass through or near the licensed
premises;
(q) storage vessels shall not be located in places which are susceptible to
flooding;
(r) the grade for the storage vessels shall be elevated slightly above the
surrounding terrain in order to ensure complete drainage of water from
beneath the bottom of the vessels; and
(s) every container, vessel or tank used for storing highly flammable liquid
or flammable liquefied or compressed gas shall be clearly and in bold
letters marked Danger — Highly Flammable Liquid " or - Danger —
Flammable liquefied or Compressed Gas ", as the case may be.
5. Design of storage vessels
(1) General: Each static vessel for the storage of flammable liquefied or
compressed gas shall be provided with the following finings and
instruments which are suitable for use at pressures not less than the
design pressure of the vessel and for the temperatures appropriate to the
worst operating conditions namely:
(a) At least two pressure safety valves connected independently to the
vapour space;
(b) Two independent liquid level indicators;
(c) A high level switch with alarm;
(d) A pressure gauge, connected to the vapour space; and
(e) a temperature gauge for measuring the temperature of the contents of
the vessel.
(2) Vessel connections: In every flammable liquefied or compressed gas
storage vessel
(i) all the connections to the vessel shall be designed and fitted in
accordance with the Design Code of Indian Standard-2825 or equivalent
duly approved by the Chief Controller of Explosives;
(ii) not more than one nozzle shall be provided at its bottom for inlet and
outlet purpose, apart from the drainage pipe
(iii) the nozzle shall be a full-welded pipe and shall extend to a minimum
distance of 3 (three) meters from the shadow of the vessel. A
combination of manual and remote operated shut-down valve shall be
provided on this bottom nozzle at a distance of atleast 3 (three) meter
beyond the shadow of the vessel. The nozzle shall have a slope of 1.5
degree ;
(iv) the nozzle shall be stress-relieved along with the vessel;
(v) (sic) there shall not be any flange, instrument tapping or manhole fitted
on this nozzle up to the combination of manual and remote operated
valve ; and
(vi) An excess flow valve shall be provided for the nozzle on the body of the
vessel.
(3) Pressure Safety Valve: In every storage vessel
(i) the pressure safety valves provided shall be of spring-loaded type
(weight-loaded safety valves shall not be used). Each of the pressure
safety valves shall have 100% (hundred percent.) relieving capacity;
(ii) the pressure safety valves shall be set to discharge at a pressure not
more than 110 (one hundred and ten) percent. of the design pressure
of the vessel and shall have a total relieving capacity adequate for
limiting the pressure build-up in the vessel not more than 120 (one
hundred and twenty) per cent. of the design pressure;
(iii) the discharge of the pressure safety valves shall be connected to flare
system. If available, In case the flare system is not available, the
discharge from the pressure safety valve shall be vented vertically
upwards to atmosphere at a minimum elevation of 3 meter above the
top of the vessel for effective dispersion of the discharge. A loose-fitting
rain cap with a non-sparking chain attached to the vent pipe shall be
fitted on top of the pressure safety valve;
(iv) an isolation valve shall be provided in between each pressure safety
valve and the vessel. The arrangement of such isolation valve shall be
so designed as to afford full required capacity flow through atleast one
of the pressure safety valves ; and
(v) each pressure safety valve shall be visibly marked with the "set
pressure" in Kg/Sq.Cm. (gauge) at which it will discharge, with its
actual rate of discharge in cubic meter per minute of the gas at a
pressure of 120 (one hundred and twenty) percent of the design
pressure of the vessel.
(4) Emergency shut-off valve: In every storage vessel
(i) all liquid and vapour connections, except those for pressure safety
valves and the drainage connections of diameter less than 25 (twenty five)
mm., shall have an emergency shut-off valve, such as an excess flow
check valve or a remote operated valve:
Provided that the emergency shut-off valve is not required in cases where
the connection to a vessel is not greater than three centimeter in diameter
for liquid and eight centimeter in diameter for vapour ;
(ii) where the emergency shut-off valve provided is of 'excess flow check
valve' type, its closing rate of flow shall be below the rate which is likely to
result due to a fracture of the line which it is protecting, calculated under
the worst conditions. Excess flow check valve shall have a flow capacity
sufficiently above the normal flow requirements to prevent valve chatter.
(5) Bottom water draw-off or drain valve-In every storage vessel
(i) there shall be provided two drain valves at the bottom of the vessel
between the remote operated valve and the first isolation valve. The
length of the pipeline between the two drain valves shall be atleast 0.5
meter to minimize the risk of simultaneous obstruction of both valves
due to freezing of any water present in the liquefied gas. The drain
connections shall be not more than 50 (fifty) millimeter in diameter;
(ii) the first drain valve from the vessel shall be of gate type (throttle type),
while the second drain valve shall be of quick shut-off type ;
(iii) the material of construction for the drain pipeline and the related
connections shall be suitable for cryogenic application.
(6) Sampling valve: In every storage vessel, two valves with suitable distance-
pipe of not less than 0.5 meter in length between them shall be fitted at its
bottom between the remote operated valve and the first isolation valve for
sampling purpose. (The provision of a distance-pipe is for the purpose of
avoiding icing problem in the up stream valve)
(7) Liquid level gauging device: In every storage vessel, out of two level
indicators provided, one shall be of "float" type and the other shall be of
"differential pressure" type in case of Horton Spheres. Magnetic float type
gauge shall be used for bullets in the place of "differential pressure" type
"High Level" alarm shall be set on the level indicators to operate at not
more than 85% (eighty five percent.) of the volumetric capacity of the
vessel. An audio-visual indication as regards the high level alarm shall be
provided at the normal place of operator's seat.
(8) Pressure gauge: In every storage vessel, there shall be provided atleast
one pressure gauge, duly calibrated and having a dial range not less than
1.5 times the design pressure, easily visible and designed to show the
correct internal pressure at all times. It shall be provided in the vapour
space at the top. A suitable stop valve shall be provided in between the
vessel and the pressure gauge.
(9) Gas sensors: In every storage vessel for flammable liquefied or
compressed gas, gas sensors with alarm shall be provided at vulnerable
areas and in the event of gas leakage, such sensor shall trip the
compressor or pump if in operation.
(10) Bonding: Electrical continuity shall be maintained between the flanges by
means of bonding in every storage vessel and its pipe lines.
(11) Pop off valves: “Pop off" valves shall be provided in between isolation
valves on the pipelines carrying flammable liquefied or compressed gases.
(12) Capacity of vaporizer: The vaporizer, connected to the flammable
liquefied gas storage vessels shall have adequate capacity to meet the
required flow rate of flammable liquefied gas in the process.
6. Prevention of ignition
In every location where highly flammable liquid or flammable
liquefied or compressed gas is stored, conveyed, handled or used or where
there is danger of fire or explosion from accumulation of highly flammable
liquid or liquefied compressed gas in air, all practicable measures shall be
taken to exclude the sources of ignition. Such precautions shall include the
following:
(a) all electrical apparatus shall either be excluded from the area of risk or
they shall be of such construction and so installed and maintained as
to prevent the danger of their being a source of ignition;
(b) effective measures shall be adopted for prevention of accumulation of
static charges to a dangerous extent;
(c) no person shall wear or be allowed to wear any footwear having iron
or steel nails or any other exposed ferrous materials which is likely to
cause sparks by friction;
(d) smoking, lighting or carrying of matches, lighters or smoking
materials shall be prohibited;
(e) transmission bolts with iron fasteners shall not be used; and
(f) all other precautions, as are reasonably practicable, shall be taken to
prevent initiation of ignition from all other possible sources such as
open flames, frictional sparks, over heated surfaces of machinery or
plant, chemical or physical-chemical reaction and radiant heat.
7. Enclosed system for conveying highly flammable liquids:
Wherever it is reasonably practicable, highly flammable liquids shall be
conveyed within a factory in totally enclosed system consisting of pipe
lines, pumps and similar appliances from the storage tank or vessel to the
point of use. Such enclosed system shall be so designed, installed,
operated and maintained as to avoid leakage or the risk of spilling.
8. Prohibition of smoking:
No person shall smoke in any place where a highly flammable liquid or
flammable liquefied or compressed gas is present in circumstances that
smoking would give rise to a risk of fire. The occupier shall take all
practicable measures to ensure compliance with this requirement including
display of a bold notices indicating prohibition of smoking at every place
where this requirement applies.
9. Fire protection:
In every factory
(1) no vehicular traffic shall be permitted within the risk area of lower
flammable limit of the highly flammable liquid or flammable liquefied or
compressed gas stored. When required, vehicles filled with approved
spark arrestors shall only be allowed with valid vehicle entry permit.
(2) all the vessels used for bulk storage or handling of highly flammable
liquid or flammable liquefied or compressed gases shall be protected
against the hazards of fire as follows:
(a)medium velocity water spray system shall be provided for all above
ground storage vessels, cylinder storage or filling or repair sheds,
pump houses, bulk lorry and tank wagon gantries;
(b) detection of fire for automatic actuation of medium velocity water
sprinkler system shall be provided at all critical locations such as bulk
storage, tank truck or tank wagon gantry, pump or compressor
house and vapourisers ;
(c) medium velocity water sprinkler system shall be based on heat and
other detection.
(d) Quartzoid Bulb protection designed to blow at 79 (seventy nine)
degree centrigrade (maximum) shall be provided in open areas or in
the sheds ;
(e) Medium velocity water sprinkler system shall function in such away
that the actuation of fire detectors shall initiate the following:
(i) opening of deluge valve;
(ii) audio-visual alarm at the fire pump house or control panel;
(iii) fire siren; and
(iv) the diesel pump will get started based on the "Set pressure" to
supplement or to maintain the fire water pressure in the ring
main; and
(f) The medium velocity water sprinkler system shall have a minimum
spray density of ten liters per minute per square meter in the case of
flammable liquefied or compressed gas and in the case of highly
flammable liquid it shall have minimum spray density of 3 (three)
liters per minute per square meter for the single largest risk area.
For the purpose of calculation of a single risk area, the following shall
be taken into account:
(i) in case of bulk storage, adjoining vessels within the distance of R
+ 30 (thirty) meter, where R is the radius of the vessel and 30
(thirty) meter shall be measured from the periphery of the vessel
(ii) in case of tank lorry gantry, a maximum of 8 (eight) bays shall be
taken as a single risk area ; and
(iii) in case of tank wagon gantry, a minimum of one gantry (600 (six
hundred) Metric Tonnes) shall be taken as a single risk area
(3) (a). a fire water ring main shall be provided all around the locations of
storage and handling of flammable liquefied or compressed gases with
hydrants or monitors spaced at 30 (thirty) meter centre to centre. Fire
hydrants and monitors shall be installed outside the licensed premises;
(b). the fire water pressure system shall be designed for a Minimum
residual pressure of 7(seven) Kgf/Sq.Cm. (gauge) at the remotest place of
application in the plant ;
(c). fire hydrant network shall be provided in closed loops to ensure multi-
directional flow in the system. Isolation valves shall be provided to enable
isolation of any section of the network without affecting the flow in the
rest; and
(d). the fire water system in the plant shall be designed to meet the
highest fire-water flow requirement of medium velocity water sprinkler for
a single largest risk area at a time plus 288 (two hundred and eighty eight)
meter/hour for operating 2 (two) numbers fire water monitor or
supplementary hose requirements.
(4)(a). water for the hydrant service shall be stored in any easily accessible
surface of underground concrete reservoir or above ground tank of steel or
concrete;
(b). the effective fire water storage capacity available for fire-fighting
shall be for four hours; and
(c). storage tank or reservoir for fire water shall be in two interconnected
compartments to facilitate cleaning and repair.
(5) Portable fire extinguishers as approved by Bureau of Indian Standards
shall be located at convenient places as indicated in the Table below :—
THE TABLE
AREA PORTABLE FIRE EXTINGUISHER
(1) (2)
1. Flammable liquefied gas or 2 Numbers 10Kg.DCP
storage vessels (each)
2.Tank wagon loading or 1 Number 10 Kg. DCP.
unloading gantries extinguisher for every 15/20
meters of gantry
3.Tank truck loading or 1 Number 10Kg.DCP, fire
unloading gantries extinguisher in each Bay and 1
Number 50 Kg. Mobile DCP
unit/gantry
The dry chemical powder used in the extinguishers shall be
potassium or Urea based or Sodium Bicarbonate as per IS: 4308. The
expellant gas ie., N2/CO2 should be of good quality.
10. Loading and unloading facilities for flammable liquefied or compressed gas:
(1) Loading: In every factory, where the loading of flammable liquefied or
compressed gas is carried on, the loading station shall consist of the
following:
(a) A filling line with an isolation valve and check valve;
(b) a vapour return line with a check valve and an isolation valve to be
connected back to the storage vessel from which the loading pump is
drawing flammable liquefied gas ;
(c) suitable loading arm or flexible hoses shall be provided at the end of
filling line and vapour return line for connecting to the tank truck
vessels or tank wagons ; and
(d) Suitable thermal pressure relief valve(s) shall be provided between the
shut-off valves to protect against excessive pressure which may
develop due to thermal expansion of the trapped liquid.
(2) Unloading: In every factory, where unloading of flammable liquefied or
compressed gas is carried on, the compressor used for unloading of
flammable liquefied gases by means of a differential pressure between the
receiving and discharging vessels by withdrawing vapour from the
receiving vessel and forcing it at high pressure into the discharging vessel
shall have the following facilities:
(a) Liquid unloading check valve line with isolation valve; and
(b) Vapour line with isolation valves;
(3) Loading and unloading operations: In every factory, where the loading or
unloading of flammable liquefied or compressed gas is carried on
(a) written operating procedures for loading or unloading operation, clearly
defining the safety checks and precautions to be observed as well as
the responsibilities of the personnel involved in such operation, shall be
prepared both in English and in Telugu and shall be given to them and
also displayed at the site;
(b) flexible hoses used for transfer of flammable liquefied or compressed
gas to or from a tank truck or tank wagon shall be,
(i) designed and constructed in accordance with the Static and Mobile
Pressure Vessels (Unfired) Rules, 1981;
(ii) having a means of identification; and
(iii) periodically checked for electrical and mechanical continuity and
recorded in the register;
(c) for connecting and disconnecting hoses, only non-sparking type of tools
shall be used;
(d) the tank truck shall have the starter motor which shall be of non-
sparking or flame-proof type;
(e) the tank truck shall be positioned on a leveled ground and blocks
(checks) shall be placed at front and rear wheels in order to prevent
the risk of accidental vehicle movement;
(f) the engine of the vehicle shall be stopped and all the electrical
equipment shall be switched off, before commencing the loading or
unloading operation;
(g) before commencing the loading or unloading operation, static charge
shall be effectively discharged by bonding and earthing of the storage
vessels and the road tankers or wagons;
(h) the road tanker or wagon shall be electrically bonded at, specified point
to the fixed grounding system;
(i) an authorised person shall supervise the transfer operation and
respond immediately in the event of an emergency;
(j) during loading operation, the pressure within the receiving tank truck
vessel shall be observed to ensure that it does not approach the" start-
to-discharge" pressure of the relief valve. Filling rate shall be regulated
as required;
(k) the receiving vessel which is having an internal pressure of less than 1
(one) Kg/Sq.Cm (g) shall not be permitted to be filled, such vessel shall
be checked for Oxygen content or explosive mixture and purged, if
necessary ;
(l) filling or transfer operation shall be done only during day time;
(m) filling or transfer operation shall be stopped immediately in the event
of —
(a) uncontrolled leakage occurring;
(b) a fire occurring in the vicinity;
(c) lightning and thunder-storm;
(n) the "Safe Operating Procedure" for unloading shall be displayed
conspicuously in English and Telugu near the unloading area.
11. Maintenance and Inspection
In every factory where highly flammable liquid or flammable liquefied
or compressed gas is stored in bulk.
(1) the storage vessels and the safety fittings and instruments shall be
tested periodically as per the requirements under various statutes as
applicable and relevant records with the particulars of such testing shall
be maintained;
(2) loading or unloading hoses shall be tested at least once in every six
months;
(3) the earth pits shall be maintained well and the earth resistance shall be
measured atleast once in every 12 (twelve) months ; and records shall
be maintained in this regard ;
(4) the foundation and supports of the storage vessels shall be checked once
in a year for differential settlement due to disturbance in the sub-soil ;
(5) the cathodic protection, if provided, shall be monitored periodically and
maintained well for its effectiveness ;
(6) the gas detection system shall be checked and calibrated periodically;
and
(7) the fire water system which includes fire water pumps, fire hydrant or
monitor, piping network and water sprinkler or deluge system shall be
checked periodically and maintained well for its fail-safe operation.
12. Training
The occupier of every factory in which highly flammable liquid or
flammable liquefied or compressed gas is stored in bulk shall ensure that
(1) the supervisory or managerial personnel are adequately trained in all
aspects of safe storage and handling of highly flammable liquid or
flammable liquefied or compressed gas as well as disaster control or
preparedness and response
(2) regular raining programmes are conducted in loading or unloading
operation, drafting procedure, commissioning and decommissioning
procedures,” hot work” permit system, fire-fighting or emergency
combat operation, health hazards etc., for
(a) regular workers;
(b) contract workers; and
(c) security staff.
(3) Full-scale emergency mockdrill, simulating leakage of flammable gas and
the consequent major fire, are conducted in the plant atleast once in every
six months in order to assess the level of preparedness and the adequacy
of combat measures. Any deviations or defects observed during such
mock- drill shall be rectified forthwith.