GENERATING PETROL GAS FROM DANGEROUS PETROLEUM
1. Prohibition relating to pregnant women and Adolescent - No pregnant woman or
adolescent shall be employed or permitted to work in or shall be allowed to enter any building
in which the generation of gas from dangerous petroleum is carried on.
2. Flame traps - The plant for generation of gas from dangerous petroleum and associated
piping and fittings shall be fitted with at least two efficient flame traps so designed and
maintained as to prevent a flash back from any burner to the plant. One of these traps shall be
fitted as close to the plant as possible. The plant and all pipes and valves shall be installed and
maintained free form leaks.
3. Generating building or room - All plants for generation of gas from dangerous
petroleum erected after the coming into force of the provisions specified in this schedule, shall
be erected outside the factory building proper in a separate well-ventilated building (hereinafter
referred to as "generating building"). In the case of such plants erected before the coming into
force of the provisions specified in this schedule, there shall be no direct communication
between the room where such plants are erected (hereinafter referred to as "the generating
room") and the remainder of the factory building. So far as practicable, all such generating
rooms shall be constructed of fire-resisting materials.
4. Fire extinguishers - An efficient means of extinguishing petrol fires shall be maintained
in an easily accessible position near the plant for generation of gas from dangerous petroleum.
5. Plant to be approved by Inspector-cum-Facilitator - Gas from dangerous petroleum
shall not be manufactured except in a plant for generating gas, the design and construction of
which has been approved by the Chief Inspector-cum-Facilitator.
6. Escape of dangerous petroleum - Effective steps shall be taken to prevent dangerous
petroleum from escaping into any drain or sewer.
7. Prohibition relating to smoking - No person shall smoke or carry matches, fire or naked
light or other means of producing a naked light or spark in the generation room or building or
in the vicinity thereof and a warning notice in the language understood by the majority of the
workers shall be posted in the factory prohibiting smoking and the carrying of matches, fire or
naked light or other means of producing a naked light or spark into such room or building.
8. Access to dangerous petroleum or container - No unauthorized person shall have access
to any dangerous petroleum or to a vessel containing or having actually contained dangerous
petroleum.
9. Electric fittings - All electric fittings shall be of flameproof construction and all electric
conductors shall either be enclosed in metal conduits or be lead-sheathed.
10. Construction of doors - All doors in the generating room or building shall be constructed
to open outwards or to slide and no door shall be locked or obstructed or fastened in a such a
manner that it cannot be easily and immediately opened from the inside while gas is being
generated and any
person is working in the generating room or building.
11. Repair of containers- No vessel that has contained dangerous petroleum shall be
repaired in a generating room or building and no repairs to any such vessel shall be undertaken
unless live steam has been blown into the vessel and until the interior is thoroughly steamed
out or other equally effective steps have been taken to ensure that it has been rendered free
from dangerous petroleum or inflammable vapour.