The Arunachal Pradesh Occupational Safety, Health and Working Conditions Rules, 2022
Schedule ‘H’(vii)
Official text
Open in the official PDF (pp. 101–102)
Tables and forms lose their layout when extracted; the PDF is the authoritative version.
GENERATION OF GAS FROM DANGEROUS PETROLEUM:
1. Prohibition relating to women and young persons- No women or young person shall be
employed or permitted to work in or shall be allowed to enter any building in which the
generation of gas from dangerous petroleum is carried on.
2. Flame traps.—The plant for generation of gas from dangerous petroleum and associated piping
and fittings shall be fitted with at least two efficient flame traps so designed and maintained
as to prevent a flash back from any burner to the plant. One of these traps shall be fitted as
close to the plant as possible. The plant and all pipes and valves shall be installed and
maintained free from leaks.
3. Generating building or room.—All plants for generation of gas from dangerous petroleum
erected after the coming into force of the provision specified in this schedule, shall be erected
outside the factory building proper in a separate well ventilated building (hereinafter referred to
as the "generating building"). In the case of such plant erected before the coming into force of
the provisions specified in this schedule, there shall be no direct communication between the
room where such plants are erected (hereinafter referred to "as the generating room") and the
remainder of the factory building. So far as practicable, all such generating rooms shall be
constructed of fire-resisting materials.
4. Fire extinguishers.—An efficient means of extinguishing petrol fires shall be maintained in any
easily accessible position near the plant for generation of gas from dangerous petroleum.
5. Plant to be approved by Chief Inspector-cum-Facilitator—Petrol gas shall not be manufactured
except in a plant for generating petrol gas the design and construction of which has been
approved by the Chief Inspector-cum-Facilitator
6. Escape of petrol.—Effective steps shall be taken to prevent petrol from escaping into any drain
or sewer.
7. Prohibition relating to smoking, etc.—No person shall smoke or carry matches, fire or naked
light or other means of producing a naked light or spark in the generating room or building or in
the vicinity thereof and warning notice in the language understood by the majority of the
employees shall be posted in the factory prohibiting smoking and the carrying of matches, fire
or naked light or other means of producing a naked light or spark into such room or building.
8. Access to petrol or containers.—No unauthorized person shall have access to any petrol or to
a vessel containing or having actually contained petrol.
9. Electric fittings.—All electric fitting shall be of flame proof construction and all electric
conductors shall either be enclosed in metal conduites or be lead-sheathed.
10. Construction of doors.—All doors in the generating room or building shall be constructed to
open outwards; or to slide and no door shall be locked or obstructed or fastened in such a
manner that it cannot be easily and immediately opened from the inside while gas is being
generated and any person is working in the generating room or building.
11. Repair of containers.—No vessel that has contained petrol shall be repaired in a generating
room or building and no repairs to any such vessels shall be undertaken unless live steam has
been blown into the vessel and until the interior thoroughly steamed out or other equally
effective steps have been taken to ensure that it has been rendered free from petrol or
inflammable vapour